Permit: T19CM01283

Parcel: 12620001C


Addresses:

200 S ALVERNON WY


Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Permit Number - T19CM01283

Inspection Description - ELECTRIC - RECONNECT

Inspection Status - Approved

Date Description Inspector Results Comments
06/09/2019 ELECTRIC - RECONNECT Approved Re-location and installation of 1200 AMP CT Meter Cabinet, New Sets of Parallel #500 MCM Conductors from Existing 120/208V Transformer to new CT Cabinet ok.
New (2) sets of Parallel #600 MCM Conductors from New CT to Existing 800AMP SES OK, LINE Side Tap Approved .System Grounded and bonded Per NEC.
Sent Verbal Clearance @ 10:45pm (RECN/DGL). Contractor to call in another inspection for Finals, Utility Disconnects not finished and to still be inspected prior to release of a Solar Meter (DGC).
$165 Check received upon arrival of inspection (AFTERHOURS)