Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
Permit Number - T19CM01283
Inspection Description - ELECTRIC - RECONNECT
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/09/2019 | ELECTRIC - RECONNECT | Approved | Re-location and installation of 1200 AMP CT Meter Cabinet, New Sets of Parallel #500 MCM Conductors from Existing 120/208V Transformer to new CT Cabinet ok. New (2) sets of Parallel #600 MCM Conductors from New CT to Existing 800AMP SES OK, LINE Side Tap Approved .System Grounded and bonded Per NEC. Sent Verbal Clearance @ 10:45pm (RECN/DGL). Contractor to call in another inspection for Finals, Utility Disconnects not finished and to still be inspected prior to release of a Solar Meter (DGC). $165 Check received upon arrival of inspection (AFTERHOURS) |