Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Details

Status:
Final
Type:
COMMERCIAL OTHER
Apply Date:
02/21/2019
Applicant:
SOLON CORPORATION ***APA***
Description:
PV SHADE CANOPIES
Contractors:
  • SOLON CORPORATION ***APA***

Permit Reviews

Permit Number - T19CM01283
Permit Status: Final
Permit Description: PV SHADE CANOPIES
Start Date Submittal Complete Date Status  
02/21/2019 COMMERCIAL - BLDG/FIRE/ZONING/ENG 03/20/2019 ACTIVE Review Details
02/21/2019 COMMERCIAL - BLDG/FIRE/ZONING/ENG 02/21/2019 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T19CM01283
Permit Status: Final
Permit Description: PV SHADE CANOPIES
Total Outstanding Activity Conditions - 1
Date Name
02/21/2019 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T19CM01283
Permit Description: PV SHADE CANOPIES
Total Completed Inspections - 11
Date Description Inspector Results Comments
05/09/2019 EXCAVATION/LAYOUT REBAR & ZON GWEST Approved 2x13 footings for 19 park and shade supports. 3 Ufers 20 wrapped
05/09/2019 ELECTRIC - UFER GWEST Approved 2x13 footings for 19 park and shade supports. 3 Ufers 20 wrapped
05/10/2019 ELECTRIC - UNDERGROUND RCHANDLER Approved
05/22/2019 ELECTRIC - INTERMEDIATE DQUINN Approved
05/22/2019 FRAMING DQUINN Approved
06/09/2019 ELECTRIC - RECONNECT DMUNIZ Approved Re-location and installation of 1200 AMP CT Meter Cabinet, New Sets of Parallel #500 MCM Conductors from Existing 120/208V Transformer to new CT Cabinet ok.
New (2) sets of Parallel #600 MCM Conductors from New CT to Existing 800AMP SES OK, LINE Side Tap Approved .System Grounded and bonded Per NEC.
Sent Verbal Clearance @ 10:45pm (RECN/DGL). Contractor to call in another inspection for Finals, Utility Disconnects not finished and to still be inspected prior to release of a Solar Meter (DGC).
$165 Check received upon arrival of inspection (AFTERHOURS)
06/11/2019 BUILDING - FINAL GWEST Approved ALL COT REQUIREMENTS COMPLETE
06/11/2019 OUTDOOR LIGHTING FINAL GWEST Approved
06/11/2019 BUILDING - FINAL GWEST Approved Approved upon meeting all COT requirements and other department approvals and sign offs.
07/22/2019 ELECTRIC - FINAL DMUNIZ Approved Clear TEP (DGC) for 200 S Alvernon, ok to close this permit.
Verbal Clearance sent in for 202 S Alvernon @ 7:59 PM (RECN).
Check for $165 received upon arrival.
08/22/2019 TEP CLEARANCE - PM AQUIROZ Approved TEPDG -13856 CODE DGC

Documents

File Name Document Type  
None LETTER OF COMPLETION VIEW