Permit: T18FC00911
Permit Details
Apply Date:
11/13/2018
Applicant:
Description:
Automatic Fire Extingshing Sys - Install new NFPA 13 fire sprinkler system; Additional Plan Reviews: 1
Outstanding Inspections
Permit Status: Expired
Permit Number: T18FC00911
Permite Description: Automatic Fire Extingshing Sys - Install new NFPA 13 fire sprinkler system; Additional Plan Reviews: 1
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/03/2019 | COT - FCON - Sprinkler - Final | N/A | Partial Pass | {Activity date: 07/03/2019; Status: Partial Approval; Inspector: JPEELDAVIS; Comment: Entered by JPEELDA1 - Need to move the lights and or adjust the fire sprinkler heads in 5 units due to light fixture and obstruction rules gaps next to escutcheons need to be patched Bldg 2 needs the riser room to have a 3' clearance around the riser} |
Completed Inspections
Permit Status: Expired
Permit Number: T18FC00911
Permit Description: Automatic Fire Extingshing Sys - Install new NFPA 13 fire sprinkler system; Additional Plan Reviews: 1
Total Completed Inspections - 1
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/04/2019 | FCON – OH Piping & Hydro | Passed | {Activity date: 03/04/2019; Status: Approved; Inspector: JPEELDAVIS; Comment: Entered by JPEELDA1 - 207 & 209 PSI on the gauges. The west building design has completely been altered since the plans that we approved were issued with a permit. Need to have ASBUILT drawings prior to final. Some of the pipe is right on the heat registers need to move away. Three-Four heads were covered in foam and need to be replaced.} |