Permit: T18FC00582
Permit Details
Status:
Final
Type:
Automatic Fire Extingshing Sys
Address:
1151 E HERMANS RD 919
Address NEW:
1151 E HERMANS RD 919
Apply Date:
07/18/2018
Applicant:
SUN MECHANICAL CONTRACTING
Description:
INSTALL DUTILE UG FIRE RISER FROM EXIST PIV TO ABOVE GROUND WITH FLANGE & BLIND FLANGE.
Completed Inspections
Permit Status: Final
Permit Number: T18FC00582
Permit Description: INSTALL DUTILE UG FIRE RISER FROM EXIST PIV TO ABOVE GROUND WITH FLANGE & BLIND FLANGE.
Total Completed Inspections - 2
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/18/2018 | FIRE SPKLR - UG PIPING FLUSH | JPEELDAVIS | Approved | Full forward flush of the 6" fire sprinkler line |
| 07/18/2018 | FIRE SPKLR - UG, PIPING, HYDRO | JPEELDAVIS | Approved | 210 PSI for two hours |