Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T18FC00338
Permit Details
Status:
Expired
Type:
Fire Construction Permit
Address:
20 E BROADWAY BL
Address NEW:
20 E BROADWAY BL
Apply Date:
04/23/2018
Applicant:
Description:
Fire Alarm & Detection Systems - MONITOR ONLY; Fire Alarm Systems - Monitor Only
Outstanding Inspections
Permit Status: Expired
Permit Number: T18FC00338
Permite Description: Fire Alarm & Detection Systems - MONITOR ONLY; Fire Alarm Systems - Monitor Only
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/15/2018 | COT - FCON - Alarm - Final | N/A | Partial Pass | {Activity date: 11/15/2018; Status: Partial Approval; Inspector: JPEELDAVIS; Comment: Entered by JPEELDA1 - 6th floor tested and approved} ; {Activity date: 10/30/2018; Status: Partial Approval; Inspector: JPEELDAVIS; Comment: Entered by JPEELDA1 - 3rd, 4th and 5th floor tested} ; {Activity date: 07/24/2018; Status: Partial Approval; Inspector: JPEELDAVIS; Comment: Entered by JPEELDA1 - Tested the Basement, 1st and 2nd floor complete fire alarm. Left the two smoke detectors located on the Jackson side enterance covered and did not test due to construction dust. Also, did not test the fire alarm devices in the stirwells due to construction dust. Tested the notification devices in the hallway on floors 3-6. 6th floor notification needs to be synchronized. Electrical rooms floors 3-6 need to be sealed and protected from construction debris prior to TCO for the Basement, 1st and 2nd floors. Water flows were as follows: Basement: 39 seconds 1st floor: 55 seconds 2nd floor: 39 seconds 3rd floor: 49 seconds 4th floor: 25 seconds 5th floor: 28 seconds 6th floor : 30 seconds} |