Inspection History Details
Inspection Status: Partial Pass
Inspection History: COT - FCON - Alarm - Final
Permit Number - T18FC00338
Inspection Description - COT - FCON - Alarm - Final
Inspection Status - Partial Pass
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/15/2018 | COT - FCON - Alarm - Final | JPEELDAVIS | Partial Approval | Entered by JPEELDA1 - 6th floor tested and approved |
| 10/30/2018 | COT - FCON - Alarm - Final | JPEELDAVIS | Partial Approval | Entered by JPEELDA1 - 3rd, 4th and 5th floor tested |
| 07/24/2018 | COT - FCON - Alarm - Final | JPEELDAVIS | Partial Approval | Entered by JPEELDA1 - Tested the Basement, 1st and 2nd floor complete fire alarm. Left the two smoke detectors located on the Jackson side enterance covered and did not test due to construction dust. Also, did not test the fire alarm devices in the stirwells due to construction dust. Tested the notification devices in the hallway on floors 3-6. 6th floor notification needs to be synchronized. Electrical rooms floors 3-6 need to be sealed and protected from construction debris prior to TCO for the Basement, 1st and 2nd floors. Water flows were as follows: Basement: 39 seconds 1st floor: 55 seconds 2nd floor: 39 seconds 3rd floor: 49 seconds 4th floor: 25 seconds 5th floor: 28 seconds 6th floor : 30 seconds |