Permit Details

Status:
Final
Type:
Fire Alarm & Detection Systems
Address NEW:
855 W CONGRESS ST
Apply Date:
01/25/2018
Applicant:
CLIMATEC BUILDING TECHNOLOGIES GROUP
Description:
INSTALLATION OF A FIRE ALARM SYSTEM WITH MONITORING.
Contractors:
  • CLIMATEC BUILDING TECHNOLOGIES GROUP

Completed Inspections

Permit Status: Final
Permit Number: T18FC00080
Permit Description: INSTALLATION OF A FIRE ALARM SYSTEM WITH MONITORING.
Total Completed Inspections - 1
Date Description Inspector Results Comments
12/20/2018 FIRE - ALARM FINAL JPEELDAVIS Approved Tested all of the waterflow and tampers. Verified the 4 floors notification devices. Monitoring verified. Need to check the following for COFO:
Room 404,402,304,307,211,206,204,201 and 202 need to replace the strobe/low frequency sounders with LF only sounders. The first floor now has the ADA rooms. Need to add the circuit disconnecting means to all the fire panels and boosters. Label the batteries with the installation date. Need to add the red lock out that reads FIRE ALARM CIRCUIT for all breakers. Submit ASBUILT fire alarm drawings and elevator records from the state elevator inspector showing that that portion passed.