Permit Details

Status:
Expired
Type:
COMMERCIAL OTHER
Address:
4826 E PIMA ST
Address NEW:
4826 E PIMA ST
Apply Date:
11/26/2018
Applicant:
SIERRA HOWAND
Description:
ELECTRICAL RECONNECT

Outstanding Activity Conditions

Permit Number - T18CM09267
Permit Status: Expired
Permit Description: ELECTRICAL RECONNECT
Total Outstanding Activity Conditions - 1
Date Name
11/26/2018 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T18CM09267
Permite Description: ELECTRICAL RECONNECT
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
ELECTRIC - FINAL N/A Not Inspected

Completed Inspections

Permit Status: Expired
Permit Number: T18CM09267
Permit Description: ELECTRICAL RECONNECT
Total Completed Inspections - 2
Date Description Inspector Results Comments
11/30/2018 ELECTRIC - RECONNECT RCHANDLER Approved 1-Label services.
2-Install weatherproof conduit connectors above bussing.
3-Seal unused openings.
4-Install antioxidant on aluminum conductors.
5-Multiple neutrals on the same lug.
6- Provide access to North service; paint has rendered it inoperable. 7-Conduit on South Service will not allow installation of dead front.
01/18/2019 TEP CLEARANCE - AM BJONES Approved RECN

Documents

File Name Document Type  
None DOCUMENTS VIEW