Permit: T18CM09267
Permit Details
Apply Date:
11/26/2018
Applicant:
SIERRA HOWAND
Description:
ELECTRICAL RECONNECT
Outstanding Activity Conditions
Permit Number - T18CM09267
Permit Status: Expired
Permit Description: ELECTRICAL RECONNECT
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 11/26/2018 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T18CM09267
Permite Description: ELECTRICAL RECONNECT
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| ELECTRIC - FINAL | N/A | Not Inspected |
Completed Inspections
Permit Status: Expired
Permit Number: T18CM09267
Permit Description: ELECTRICAL RECONNECT
Total Completed Inspections - 2
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/30/2018 | ELECTRIC - RECONNECT | RCHANDLER | Approved | 1-Label services. 2-Install weatherproof conduit connectors above bussing. 3-Seal unused openings. 4-Install antioxidant on aluminum conductors. 5-Multiple neutrals on the same lug. 6- Provide access to North service; paint has rendered it inoperable. 7-Conduit on South Service will not allow installation of dead front. |
| 01/18/2019 | TEP CLEARANCE - AM | BJONES | Approved | RECN |