Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T17FC01034
Permit Details
Apply Date:
12/19/2017
Applicant:
N/A
Description:
NEW FIRE SPRINKLER SYSTEM NO U.G.
Completed Inspections
Permit Status: Final
Permit Number: T17FC01034
Permit Description: NEW FIRE SPRINKLER SYSTEM NO U.G.
Total Completed Inspections - 3
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/28/2018 | FIRE SPKLR - FINAL | JPEELDAVIS | Approved | ONLY PARTIAL FOR 3rd & 4th FLOOR- 3rd floor NE office needs head moved 3rd floor middle south office needs head added 3rd floor by restroom under duct need to be moved 3rd floor west side pilar by floating board needs head added 3rd floor west office 318 needs head added 3rd floor west office behind elevator room 327 needs head added 4th floor west room under duct needs to be moved 4th floor east office by room 434 needs to be lowered 4th floor east middle duct needs raised # 432 4th floor outside executive office raise head Tested all water flow and tampers 1st floor flow - 56 seconds 2nd floor flow - 52 seconds 3rd floor flow - 52 seconds 4th floor flow - 51 seconds 5th floor flow - 46 seconds |
06/28/2018 | FIRE SPKLR - OH PIPING & HYDRO | JPEELDAVIS | Approved | |
07/06/2018 | FIRE PUMP - FINAL | gsereno1 | Approved |