Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
Permit Number - T17FC01034
Inspection Description - FIRE SPKLR - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/22/2019 | FIRE SPKLR - FINAL | Approved | approved per JPD, building and gregg from AAA | |
06/28/2018 | FIRE SPKLR - FINAL | Partial Approval | ONLY PARTIAL FOR 3rd & 4th FLOOR- 3rd floor NE office needs head moved 3rd floor middle south office needs head added 3rd floor by restroom under duct need to be moved 3rd floor west side pilar by floating board needs head added 3rd floor west office 318 needs head added 3rd floor west office behind elevator room 327 needs head added 4th floor west room under duct needs to be moved 4th floor east office by room 434 needs to be lowered 4th floor east middle duct needs raised # 432 4th floor outside executive office raise head Tested all water flow and tampers 1st floor flow - 56 seconds 2nd floor flow - 52 seconds 3rd floor flow - 52 seconds 4th floor flow - 51 seconds 5th floor flow - 46 seconds |