Permit: T17FC00717
Permit Details
Status:
Final
Type:
Automatic Fire Extingshing Sys
Address:
620 W WILLIAMS ST
Address NEW:
620 W WILLIAMS ST
Apply Date:
08/30/2017
Applicant:
KAZAL FIRE PROTECTION INC ,
Description:
INSTALL NEW WET PIPE FIRE SPRINKLER SYSTEM
Contractors:
- KAZAL FIRE PROTECTION INC ,
Completed Inspections
Permit Status: Final
Permit Number: T17FC00717
Permit Description: INSTALL NEW WET PIPE FIRE SPRINKLER SYSTEM
Total Completed Inspections - 4
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/03/2017 | FIRE SPKLR - UG PIPING FLUSH | JPEELDAVIS | Approved | |
| 11/03/2017 | FIRE SPKLR - UG, PIPING, HYDRO | JPEELDAVIS | Approved | |
| 12/28/2017 | FIRE SPKLR - FINAL | jvincent | Approved | 1) bell not wired correctly. 2) label bell breaker "fire bell." 3) add lockout to fire bell circuit breaker. 4) missing fdc. needs to be installed. 5) need knox fdc plug for fdc. 6) still need to flow water on next inspection. main drain test and inspectors test. 7) add calc plate to riser. 8) need spare head box mounted with heads and wrench inside. 9) system needs to be monitored. Charlie 591-3943 |
| 12/28/2017 | FIRE SPKLR - OH PIPING & HYDRO | jvincent | Approved | consult with harvey, not needed. |