Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/19/2018 | FIRE SPKLR - FINAL | Approved | ||
| 12/28/2017 | FIRE SPKLR - FINAL | Denied | 1) bell not wired correctly. 2) label bell breaker "fire bell." 3) add lockout to fire bell circuit breaker. 4) missing fdc. needs to be installed. 5) need knox fdc plug for fdc. 6) still need to flow water on next inspection. main drain test and inspectors test. 7) add calc plate to riser. 8) need spare head box mounted with heads and wrench inside. 9) system needs to be monitored. Charlie 591-3943 |