Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Expired
Type:
Fire Construction Permit
Address NEW:
1620 W VALENCIA RD
Apply Date:
08/18/2017
Applicant:
Description:
Automatic Fire Extingshing Sys - To Install 1 Ansul System nozzle to cover new fryer; Commercial Cooking Suppression - New System: 1; Additional Inspections: 1

Outstanding Inspections

Permit Status: Expired
Permit Number: T17FC00682
Permite Description: Automatic Fire Extingshing Sys - To Install 1 Ansul System nozzle to cover new fryer; Commercial Cooking Suppression - New System: 1; Additional Inspections: 1
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
12/20/2017 COT - FCON - Hood System - Final N/A Re-inspection required {Activity date: 12/20/2017; Status: Denied; Inspector: jvincent; Comment: Entered by JVINCEN1 - They decided to add a second link. Plans now match all equipment. Appliances did not shut down when link was cut. Micro switch works but needs to be adjusted. Also, connections to micro switch need to made outside of the box. Reinspection fee added. Must be paid prior to next inspection.} ; {Activity date: 10/03/2017; Status: Partial Approval; Inspector: jvincent; Comment: Entered by JVINCEN1 - need as-builts. plans show link over each fryer. actual, one link over one piece fryer.}

Documents

File Name Document Type  
001_FIRE PLAN.TIF FIRE PLANS VIEW
None DOCUMENTS VIEW