Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Re-inspection required
Inspection History: COT - FCON - Hood System - Final
| Date |
Description |
Inspector |
Results |
Comments |
| 12/20/2017 |
COT - FCON - Hood System - Final |
jvincent |
Denied |
Entered by JVINCEN1 - They decided to add a second link. Plans now match all equipment. Appliances did not shut down when link was cut. Micro switch works but needs to be adjusted. Also, connections to micro switch need to made outside of the box. Reinspection fee added. Must be paid prior to next inspection. |
| 10/03/2017 |
COT - FCON - Hood System - Final |
jvincent |
Partial Approval |
Entered by JVINCEN1 - need as-builts. plans show link over each fryer. actual, one link over one piece fryer. |