Permit: T17FC00255
Permit Details
Apply Date:
03/29/2017
Applicant:
SIMPLEX GRINNELL L P
Description:
Fire Alarm System Repair
Contractors:
- SIMPLEX GRINNELL L P
Completed Inspections
Permit Status: Final
Permit Number: T17FC00255
Permit Description: Fire Alarm System Repair
Total Completed Inspections - 1
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/29/2017 | FIRE - ALARM FINAL | JPEELDAVIS | Approved | duct detector room 45 did not shut down properly. duct detctor in the kitchen did not shut down properly. Smoke detectors need to be within 5' of the doors. 42 seconds waterflow heats, smoke detectors, manual pull stations and remote annunciators. |