Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/09/2018 | FIRE - ALARM FINAL | Approved | ||
| 08/29/2017 | FIRE - ALARM FINAL | Partial Approval | duct detector room 45 did not shut down properly. duct detctor in the kitchen did not shut down properly. Smoke detectors need to be within 5' of the doors. 42 seconds waterflow heats, smoke detectors, manual pull stations and remote annunciators. |