Permit: T17CM07418
Permit Details
Apply Date:
09/28/2017
Applicant:
A23 STUDIOS
Description:
OFFICE
Architects:
- A23 STUDIOS
Permit Reviews
Permit Number - T17CM07418
Permit Status: C of o
Permit Description: OFFICE
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
09/28/2017 | COMMERCIAL - TI | 10/06/2017 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T17CM07418
Permit Status: C of o
Permit Description: OFFICE
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
09/28/2017 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: C of o
Permit Number: T17CM07418
Permit Description: OFFICE
Total Completed Inspections - 21
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/22/2017 | PLUMBING - ROUGH, SOIL | RGREENE | Approved | |
12/08/2017 | PLUMBING - INTERMEDIATE | TVALENC1 | Approved | IVRS - Inspection :* |
12/08/2017 | ELECTRIC - INTERMEDIATE | TVALENC1 | Approved | IVRS - Inspection :* |
12/18/2017 | BUILDING ABOVE CEILING | aquiroz | Approved | |
12/18/2017 | MECHANICAL - ABOVE CEILING | aquiroz | Approved | |
12/18/2017 | PLUMBING - ABOVE CEILING | aquiroz | Approved | |
12/18/2017 | ELECTRIC - ABOVE CEILING | aquiroz | Approved | |
12/29/2017 | PLUMBING - PROGRESS | rbaldwin | Approved | |
12/29/2017 | MECHANICAL - INTERMEDIATE | rbaldwin | Approved | |
12/29/2017 | SHEET ROCK NAILING | rbaldwin | Approved | |
12/29/2017 | FRAMING | rbaldwin | Approved | |
12/29/2017 | BUILDING - PROGRESS | rbaldwin | Approved | |
12/29/2017 | CERTIFICATE OF OCCUPANCY | rbaldwin | Approved | |
12/29/2017 | BUILDING - FINAL | rbaldwin | Approved | |
12/29/2017 | MECHANICAL - FINAL | rbaldwin | Approved | |
12/29/2017 | PLUMBING - FINAL | rbaldwin | Approved | |
12/29/2017 | ELECTRIC - FINAL | rbaldwin | Approved | |
12/29/2017 | FIRE SPKLR - FINAL | rbaldwin | Approved | |
12/29/2017 | ENGINEERING - FINAL | RLEDONNE | Approved | |
12/29/2017 | FIRE - FINAL | jvincent | Approved | 1) Mount 12" address numbers. 2) Replace two painted sprinkler heads (reception and staff restroom) 3) Need schedules for electrical panels or label each breaker. 4) Mount extinguisher in front reception area. 5) Fire alarm in "trouble." Needs service. 6) New control valve not wired. Not currently monitored. Needs to be wired and monitored. We need to verify signal once connected. 7) Need annual inspection report for sprinkler monitoring panel/alrarm/system. No tag on panel. Unknown when it was serviced last. Any deficiency on report needs to be resolved. 8) Waiting on copy of UL cert for monitoring company which is Avantguard monitoring. Approved to obtain TCO for full occupancy. |
12/29/2017 | FIRE SPKLR - FINAL | jvincent | Approved | -replace two painted heads (reception and staff restroom) |