Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T17CM07418
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/02/2018 | FIRE - FINAL | Approved | ||
01/03/2018 | FIRE - FINAL | Partial Approval | Approved to obtain TCO. Must obtain TCO for occupancy of any type. Reinspection fee added to this permit. Must be paid prior to calling in the next inspection. Need to add suite numbers on front doors. Need permit for replacement of the control valve. Need permit for change of fire alarm monitoring. Need to verify signals with the new fire alarm company (Central ) Need to verify that the alarm power is a dedicated circuit and not shared with anything else. Need a copy of the annual fire alarm inspection report. Need to verify electrical panel schedules. |
|
12/29/2017 | FIRE - FINAL | Partial Approval | 1) Mount 12" address numbers. 2) Replace two painted sprinkler heads (reception and staff restroom) 3) Need schedules for electrical panels or label each breaker. 4) Mount extinguisher in front reception area. 5) Fire alarm in "trouble." Needs service. 6) New control valve not wired. Not currently monitored. Needs to be wired and monitored. We need to verify signal once connected. 7) Need annual inspection report for sprinkler monitoring panel/alrarm/system. No tag on panel. Unknown when it was serviced last. Any deficiency on report needs to be resolved. 8) Waiting on copy of UL cert for monitoring company which is Avantguard monitoring. Approved to obtain TCO for full occupancy. |