Permit Details

Status:
Expired
Type:
SINGLE FAMILY OTHER
Apply Date:
07/11/2017
Applicant:
WILLIAMSONS HEATING AND COOLING INC ** APA **
Description:
SPLIT SYSTEM/ REPLACE WATER HEATER
Contractors:
  • WILLIAMSONS HEATING AND COOLING INC ** APA **

Permit Reviews

Permit Number - T17CM05323
Permit Status: Expired
Permit Description: SPLIT SYSTEM/ REPLACE WATER HEATER
Start Date Submittal Complete Date Status  
07/11/2017 WALK THRU - RES 07/12/2017 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T17CM05323
Permit Status: Expired
Permit Description: SPLIT SYSTEM/ REPLACE WATER HEATER
Total Outstanding Activity Conditions - 1
Date Name
07/11/2017 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T17CM05323
Permite Description: SPLIT SYSTEM/ REPLACE WATER HEATER
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
09/22/2017 MECHANICAL - FINAL N/A Denied COLD WATER PVC AND COPPER FLEX NOT ALLOWED ON T&P DRAIN.
REMOVE THE SHIM FROM BEHIND WATER HEATER AND PROPERLY SUPPORT WATER HEATER.
TIGHTEN ROMEX CONNECTOR ONTO CORDS AT FURNACE.
PROVIDE TAMPER PROOF CAPS AT CONDENSOR.
#8 WIRE REQUIRED FOR 40 AMP AT CONDENSOR.