Inspection History Details
Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/22/2017 | MECHANICAL - FINAL | Denied | COLD WATER PVC AND COPPER FLEX NOT ALLOWED ON T&P DRAIN. REMOVE THE SHIM FROM BEHIND WATER HEATER AND PROPERLY SUPPORT WATER HEATER. TIGHTEN ROMEX CONNECTOR ONTO CORDS AT FURNACE. PROVIDE TAMPER PROOF CAPS AT CONDENSOR. #8 WIRE REQUIRED FOR 40 AMP AT CONDENSOR. |
|
| 09/21/2017 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999 * |