Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T17CM04934
Permit Details
Apply Date:
06/23/2017
Applicant:
NORDBROCK HEATHER J
Description:
Verify electric panel per T17DV01939
Outstanding Activity Conditions
Permit Number - T17CM04934
Permit Status: Expired
Permit Description: Verify electric panel per T17DV01939
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
06/23/2017 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T17CM04934
Permite Description: Verify electric panel per T17DV01939
Total Outstanding Inspections - 1
Last Inspection Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/11/2017 | ELECTRIC - FINAL | N/A | Not ready for Inspection | Incomplete inspection, 200 amp service installed without inspection, missing UFER, communication wires run in panel, service entrance conductors undersized, panel appears to be overloaded, provide load calcuations. Back fed 60 amp breaker not secured in place, PVC not permitted from meter socket to panel, have quaified electrician evalate this installation. |