Permit: T17CM02602
Permit Details
Status:
Expired
Type:
COMMERCIAL ALTERATION
Address:
2545 N CAMPBELL AV
Address NEW:
2545 N CAMPBELL AV
Apply Date:
04/04/2017
Applicant:
ARIZONA FIRE PROTECTION INC ,
Description:
INSTALL HOOD FIRE SYSTEM
Contractors:
- ANOZIRA FIRE PROTECTION L L C
Permit Reviews
Permit Number - T17CM02602
Permit Status: Expired
Permit Description: INSTALL HOOD FIRE SYSTEM
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 04/04/2017 | WALK THRU - COMM | 04/04/2017 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T17CM02602
Permit Status: Expired
Permit Description: INSTALL HOOD FIRE SYSTEM
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 04/04/2017 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T17CM02602
Permite Description: INSTALL HOOD FIRE SYSTEM
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/21/2017 | MECHANICAL - FINAL | N/A | Denied | FOR LARGE HOOD PROVIDE 16GA WELDED DUCT TO TOP OF EXHAUST FAN BASE W/GASKET UNDER FAN.SMALL HOOD REQUIRED TO BE TYPE 1 WITH GREASE DUCT TO FAN ON ROOF. NEEDS HOLE IN WALL REPAIRED. INTERLOCK FANS WITH MAKEUP AIR. TYPE 1 FANNS MUST BE HARD WIRED. |