Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 04/21/2017 |
MECHANICAL - FINAL |
|
Denied |
FOR LARGE HOOD PROVIDE 16GA WELDED DUCT TO TOP OF EXHAUST FAN BASE W/GASKET UNDER FAN.SMALL HOOD REQUIRED TO BE TYPE 1 WITH GREASE DUCT TO FAN ON ROOF. NEEDS HOLE IN WALL REPAIRED. INTERLOCK FANS WITH MAKEUP AIR. TYPE 1 FANNS MUST BE HARD WIRED. |