Permit: T16FC00354
Permit Details
Apply Date:
12/29/2016
Applicant:
CINTAS FIRE PROTECTION
Description:
Re-pipe existing fire supression system to meet current needs
Contractors:
- CINTAS FIRE PROTECTION
Completed Inspections
Permit Status: Closed
Permit Number: T16FC00354
Permit Description: Re-pipe existing fire supression system to meet current needs
Total Completed Inspections - 2
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/29/2017 | FIRE - KITCHEN EXH HOOD FINAL | jvincent | Approved | Denied. Need to change out conduit. Did not trip first time. Second trip too slow. Conduit clogged with grease build up. Nozzles over range too high. |
12/29/2017 | FIRE - KITCHEN EXH HOOD FINAL | jvincent | Approved | Approved. Still need the following two items before permit finaled. 1) Extra RI fee added. Needs to be paid for permit to be finaled. 2) Hood needs to be interconnected with FACP (sprinkler monitoring). This permit will be left open until I know which company is doing the work. |