Inspection History: FIRE - KITCHEN EXH HOOD FINAL
Permit Number - T16FC00354
Inspection Description - FIRE - KITCHEN EXH HOOD FINAL
Inspection Status - Closed
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/13/2022 | FIRE - KITCHEN EXH HOOD FINAL | Closed | PERMIT CLOSED CONTRACTOR DID NOT CALL IN INSPECTION. SYSTEM NOT VERIFIED. | |
12/28/2021 | FIRE - KITCHEN EXH HOOD FINAL | Cancelled | to re-open the permit | |
12/29/2017 | FIRE - KITCHEN EXH HOOD FINAL | Partial Approval | Approved. Still need the following two items before permit finaled. 1) Extra RI fee added. Needs to be paid for permit to be finaled. 2) Hood needs to be interconnected with FACP (sprinkler monitoring). This permit will be left open until I know which company is doing the work. |
|
12/29/2017 | FIRE - KITCHEN EXH HOOD FINAL | Denied | Denied. Need to change out conduit. Did not trip first time. Second trip too slow. Conduit clogged with grease build up. Nozzles over range too high. |