Permit: T16FC00320
Permit Details
Apply Date:
12/15/2016
Applicant:
SIMPLEX GRINNELL L P
Description:
Installation of New Fire Alarm System
Contractors:
- SIMPLEX GRINNELL L P
Completed Inspections
Permit Status: Closed
Permit Number: T16FC00320
Permit Description: Installation of New Fire Alarm System
Total Completed Inspections - 1
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/28/2016 | FIRE - ALARM FINAL | JPEELDAVIS | Approved | Need to add coverage to the ADA Rooms for compliance. Provide proof that the monitoring company is UL and or FM for fire. Elevator inspector approved the smoke and heat detector for fire fighter recall. Tested the watre flow, tampers, smoke detectors. and notification devices. Ground Flow = 60 seconds adjusted the flow switch 1st Floor Flow = 38 Seconds 2nd Flooe Flow = 37 Seconds |