Permit Details

Status:
Closed
Type:
Fire Alarm & Detection Systems
Address:
383 S STONE AV
Apply Date:
12/15/2016
Applicant:
SIMPLEX GRINNELL L P
Description:
Installation of New Fire Alarm System
Contractors:
  • SIMPLEX GRINNELL L P

Completed Inspections

Permit Status: Closed
Permit Number: T16FC00320
Permit Description: Installation of New Fire Alarm System
Total Completed Inspections - 1
Date Description Inspector Results Comments
12/28/2016 FIRE - ALARM FINAL JPEELDAVIS Approved Need to add coverage to the ADA Rooms for compliance.

Provide proof that the monitoring company is UL and or FM for fire.

Elevator inspector approved the smoke and heat detector for fire fighter recall.

Tested the watre flow, tampers, smoke detectors. and notification devices.

Ground Flow = 60 seconds adjusted the flow switch
1st Floor Flow = 38 Seconds
2nd Flooe Flow = 37 Seconds