Inspection History: FIRE - ALARM FINAL

Permit Number - T16FC00320

Inspection Description - FIRE - ALARM FINAL

Inspection Status - Closed

Date Description Inspector Results Comments
10/13/2022 FIRE - ALARM FINAL Closed PERMIT CLOSED CONTRACTOR DID NOT CALL IN INSPECTION. SYSTEM NOT VERIFIED.
01/25/2017 FIRE - ALARM FINAL Partial Approval approved ADA rooms. waiting on ROC/72 for full approval.
12/28/2016 FIRE - ALARM FINAL Partial Approval Need to add coverage to the ADA Rooms for compliance.

Provide proof that the monitoring company is UL and or FM for fire.

Elevator inspector approved the smoke and heat detector for fire fighter recall.

Tested the watre flow, tampers, smoke detectors. and notification devices.

Ground Flow = 60 seconds adjusted the flow switch
1st Floor Flow = 38 Seconds
2nd Flooe Flow = 37 Seconds