Inspection History Details
Inspection Status: Closed
Inspection History: FIRE - ALARM FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/13/2022 | FIRE - ALARM FINAL | Closed | PERMIT CLOSED CONTRACTOR DID NOT CALL IN INSPECTION. SYSTEM NOT VERIFIED. | |
| 01/25/2017 | FIRE - ALARM FINAL | Partial Approval | approved ADA rooms. waiting on ROC/72 for full approval. | |
| 12/28/2016 | FIRE - ALARM FINAL | Partial Approval | Need to add coverage to the ADA Rooms for compliance. Provide proof that the monitoring company is UL and or FM for fire. Elevator inspector approved the smoke and heat detector for fire fighter recall. Tested the watre flow, tampers, smoke detectors. and notification devices. Ground Flow = 60 seconds adjusted the flow switch 1st Floor Flow = 38 Seconds 2nd Flooe Flow = 37 Seconds |