Description:
MO8 - Installation of Fire Alarm System
Contractors:
  • ADVANCED CONTROLS CORPORATION

Completed Inspections

Permit Status: Final
Permit Number: T16FC00289
Permit Description: MO8 - Installation of Fire Alarm System
Total Completed Inspections - 1
Date Description Inspector Results Comments
12/21/2016 FIRE - ALARM FINAL JPEELDAVIS Approved Duct smoke detectors do not have good access. NFPA 72 2010 14.4.5.1 (need to provide access)
Need to chech SW side back door area for proper coverage once the building is opened and fire alarm system is complete.
Tested
Water flow south 37 seconds
Waterflow north 37 seconds
Confirmed ground fault monitoring, notification devices, batteries, smoke detectors, heat detectors and tamper switch.

Need to label riser room and inspectors test valve doors.

Could not test the duct smoke detectors. Will allow for the fire watch to end but need communication as soon as possible regarding the duct smoke detectors.