Permit: T16FC00289
Permit Details
Status:
Final
Type:
Fire Alarm & Detection Systems
Address:
3301 E GLOBAL LP
Address NEW:
3301 E GLOBAL LP
Apply Date:
12/02/2016
Applicant:
ADVANCED CONTROLS CORPORATION
Description:
MO8 - Installation of Fire Alarm System
Contractors:
- ADVANCED CONTROLS CORPORATION
Completed Inspections
Permit Status: Final
Permit Number: T16FC00289
Permit Description: MO8 - Installation of Fire Alarm System
Total Completed Inspections - 1
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/21/2016 | FIRE - ALARM FINAL | JPEELDAVIS | Approved | Duct smoke detectors do not have good access. NFPA 72 2010 14.4.5.1 (need to provide access) Need to chech SW side back door area for proper coverage once the building is opened and fire alarm system is complete. Tested Water flow south 37 seconds Waterflow north 37 seconds Confirmed ground fault monitoring, notification devices, batteries, smoke detectors, heat detectors and tamper switch. Need to label riser room and inspectors test valve doors. Could not test the duct smoke detectors. Will allow for the fire watch to end but need communication as soon as possible regarding the duct smoke detectors. |