Permit: T16FC00289

Parcel: 140290290


Addresses:

3301 E GLOBAL LP

Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Date Description Inspector Results Comments
03/17/2017 FIRE - ALARM FINAL Approved
02/25/2017 FIRE - ALARM FINAL Partial Approval Need to add one horn strobe to the midwest side of the building. Wire the fire sprinkler bell.
12/21/2016 FIRE - ALARM FINAL Partial Approval Duct smoke detectors do not have good access. NFPA 72 2010 14.4.5.1 (need to provide access)
Need to chech SW side back door area for proper coverage once the building is opened and fire alarm system is complete.
Tested
Water flow south 37 seconds
Waterflow north 37 seconds
Confirmed ground fault monitoring, notification devices, batteries, smoke detectors, heat detectors and tamper switch.

Need to label riser room and inspectors test valve doors.

Could not test the duct smoke detectors. Will allow for the fire watch to end but need communication as soon as possible regarding the duct smoke detectors.
12/20/2016 FIRE - ALARM FINAL Denied Fire alarm not monitored cannot test.
12/19/2016 FIRE - ALARM FINAL Denied Fire alarm not monitored cannot test.
12/16/2016 FIRE - ALARM FINAL Denied Fire alarm not monitored cannot test.