Permit Details

Status:
Final
Type:
Fire Alarm & Detection Systems
Apply Date:
11/29/2016
Applicant:
CLIMATEC BUILDING TECHNOLOGIES GROUP ***APA***
Description:
14 device remodel of existing fire alarm system
Contractors:
  • CLIMATEC BUILDING TECHNOLOGIES GROUP ***APA***

Completed Inspections

Permit Status: Final
Permit Number: T16FC00272
Permit Description: 14 device remodel of existing fire alarm system
Total Completed Inspections - 1
Date Description Inspector Results Comments
12/22/2016 FIRE - ALARM FINAL JPEELDAVIS Approved NFPA 72 2010 18.5.4.1 Wall-mounted appliances shall be mounted such that the entire lens is not less than 80 in (203 m) and not greater than 96 in (2.44m) above the finished floor (AFF) at the mounting height specified using the performance based alternative.

Move all notification devices up 2-3 inches to meet the requirements.