Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T16FC00272
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/10/2017 | FIRE - ALARM FINAL | Approved | Monitoring contract provided | |
12/22/2016 | FIRE - ALARM FINAL | Denied | NFPA 72 2010 18.5.4.1 Wall-mounted appliances shall be mounted such that the entire lens is not less than 80 in (203 m) and not greater than 96 in (2.44m) above the finished floor (AFF) at the mounting height specified using the performance based alternative. Move all notification devices up 2-3 inches to meet the requirements. |
|
12/14/2016 | FIRE - ALARM FINAL | Denied | 1. No one on site for 12pm appt. 2. Called contrator several times and no answer. |
|
01/09/2016 | FIRE - ALARM FINAL | Partial Approval | 509.1 Identification - Fire protection equipement shall be identified in an approved manner. "FACP Room" sign needed on door "Inspectors Test Valve" sign needed on door. 907.6.5 Monitoring - Fire alarm systems required by this chapter or by the International Building Code shall be monitored by an approved supervising station in accordance with NFPA 72. |