Permit: T16FC00272

Parcel: 110120920

Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Permit Number - T16FC00272

Inspection Description - FIRE - ALARM FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/10/2017 FIRE - ALARM FINAL Approved Monitoring contract provided
12/22/2016 FIRE - ALARM FINAL Denied NFPA 72 2010 18.5.4.1 Wall-mounted appliances shall be mounted such that the entire lens is not less than 80 in (203 m) and not greater than 96 in (2.44m) above the finished floor (AFF) at the mounting height specified using the performance based alternative.

Move all notification devices up 2-3 inches to meet the requirements.
12/14/2016 FIRE - ALARM FINAL Denied 1. No one on site for 12pm appt.
2. Called contrator several times and no answer.
01/09/2016 FIRE - ALARM FINAL Partial Approval 509.1 Identification - Fire protection equipement shall be identified in an approved manner.
"FACP Room" sign needed on door
"Inspectors Test Valve" sign needed on door.
907.6.5 Monitoring - Fire alarm systems required by this chapter or by the International Building Code shall be monitored by an approved supervising station in accordance with NFPA 72.