Permit: T16FC00267
Permit Details
Apply Date:
11/28/2016
Applicant:
CENTRAL ALARM OF TUCSON** APA
Description:
Install a cell transmitter to monitor fire sprinkler riser in the basement
Contractors:
- CENTRAL ALARM OF TUCSON** APA
Completed Inspections
Permit Status: Final
Permit Number: T16FC00267
Permit Description: Install a cell transmitter to monitor fire sprinkler riser in the basement
Total Completed Inspections - 1
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/05/2017 | FIRE - ALARM FINAL | JPEELDAVIS | Approved | Fire sprinkler water flow - 34 seconds. Tested the fire sprinkler flow, tamper, manual pull station, smoke detector above FACP, notification device, battery and AC loss. Monitoring station has the tamper programmed as a "trouble" asked that they send proof that the item was corrected to "supervisory" via e-mail. |