Description:
Install a cell transmitter to monitor fire sprinkler riser in the basement
Contractors:
  • CENTRAL ALARM OF TUCSON** APA

Completed Inspections

Permit Status: Final
Permit Number: T16FC00267
Permit Description: Install a cell transmitter to monitor fire sprinkler riser in the basement
Total Completed Inspections - 1
Date Description Inspector Results Comments
01/05/2017 FIRE - ALARM FINAL JPEELDAVIS Approved Fire sprinkler water flow - 34 seconds.
Tested the fire sprinkler flow, tamper, manual pull station, smoke detector above FACP, notification device, battery and AC loss. Monitoring station has the tamper programmed as a "trouble" asked that they send proof that the item was corrected to "supervisory" via e-mail.