Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/05/2017 | FIRE - ALARM FINAL | Approved | Fire sprinkler water flow - 34 seconds. Tested the fire sprinkler flow, tamper, manual pull station, smoke detector above FACP, notification device, battery and AC loss. Monitoring station has the tamper programmed as a "trouble" asked that they send proof that the item was corrected to "supervisory" via e-mail. |