Permit: T16FC00267

Parcel: 12810069C


Addresses:

432 S WILLIAMS BL


Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Permit Number - T16FC00267

Inspection Description - FIRE - ALARM FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/05/2017 FIRE - ALARM FINAL Approved Fire sprinkler water flow - 34 seconds.
Tested the fire sprinkler flow, tamper, manual pull station, smoke detector above FACP, notification device, battery and AC loss. Monitoring station has the tamper programmed as a "trouble" asked that they send proof that the item was corrected to "supervisory" via e-mail.