Permit Details

Status:
Final
Type:
Fire Alarm & Detection Systems
Apply Date:
10/07/2016
Applicant:
SIMPLEX GRINNELL L P
Description:
Generations@ Park Mall - addition to existing fire alarm system
Contractors:
  • SIMPLEX GRINNELL L P

Completed Inspections

Permit Status: Final
Permit Number: T16FC00110
Permit Description: Generations@ Park Mall - addition to existing fire alarm system
Total Completed Inspections - 1
Date Description Inspector Results Comments
12/12/2016 FIRE - ALARM FINAL JPEELDAVIS Approved duct smoke detector required a lift for access. Tested the detector via the test sitch. Operations per matrix did operate. Will test actual function for annual in February. FACP Breaker to be RED.

Documents

File Name Document Type  
001_ALARM.TIF FIRE PLANS VIEW
002_ALARM.TIF FIRE PLANS VIEW
003_ALARM.TIF FIRE PLANS VIEW