Permit: T16FC00110

Parcel: 12801005H


Addresses:

5870 E BROADWAY BL


Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Permit Number - T16FC00110

Inspection Description - FIRE - ALARM FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/29/2017 FIRE - ALARM FINAL Approved JMPD approved 12-12-2016 FINAL today in the computer
12/12/2016 FIRE - ALARM FINAL Approved duct smoke detector required a lift for access. Tested the detector via the test sitch. Operations per matrix did operate. Will test actual function for annual in February. FACP Breaker to be RED.
12/09/2016 FIRE - ALARM FINAL Denied 1) Did not test anything. Not ready.
2) AC unit was not on so we could not test duct function.
3) Strobes were working but not the horns.
4) Needs full acceptance test.
5) Contractors permit T16CM07032