Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T16FC00110
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/29/2017 | FIRE - ALARM FINAL | Approved | JMPD approved 12-12-2016 FINAL today in the computer | |
12/12/2016 | FIRE - ALARM FINAL | Approved | duct smoke detector required a lift for access. Tested the detector via the test sitch. Operations per matrix did operate. Will test actual function for annual in February. FACP Breaker to be RED. | |
12/09/2016 | FIRE - ALARM FINAL | Denied | 1) Did not test anything. Not ready. 2) AC unit was not on so we could not test duct function. 3) Strobes were working but not the horns. 4) Needs full acceptance test. 5) Contractors permit T16CM07032 |