Permit: T16CM07411
Permit Details
Status:
Expired
Type:
MULTI FAMILY OTHER
Address:
5737 S MORRIS BL #E
Address NEW:
5737 S MORRIS BL #E
Apply Date:
09/27/2016
Applicant:
BRITTENHAM SCOTT
Description:
ELECTRIC RECONNECT
Outstanding Activity Conditions
Permit Number - T16CM07411
Permit Status: Expired
Permit Description: ELECTRIC RECONNECT
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 09/27/2016 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T16CM07411
Permite Description: ELECTRIC RECONNECT
Total Outstanding Inspections - 2
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/01/2016 | ELECTRIC - RECONNECT | N/A | Denied | 1-light fixtures missing on exterior, bare wiring exposed 2-water heater missing (required for occupancy), water heater wiring wiring exposed and hanging out of wall 3-wiring in subpanel not to code 4-smoke alarm in living area not installed per manuf. instructions 5-smoke alarm required in bedroom 6-verify building is permitted for occupancy 7-this building appears to have been the laundry room |
| 11/01/2016 | ELECTRIC - FINAL | N/A | Denied | 1-light fixtures missing on exterior, bare wiring exposed 2-water heater missing (required for occupancy), water heater wiring wiring exposed and hanging out of wall 3-wiring in subpanel not to code 4-smoke alarm in living area not installed per manuf. instructions 5-smoke alarm required in bedroom 6-verify building is permitted for occupancy 7-this building appears to have been the laundry room |