Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/01/2016 | ELECTRIC - FINAL | Denied | 1-light fixtures missing on exterior, bare wiring exposed 2-water heater missing (required for occupancy), water heater wiring wiring exposed and hanging out of wall 3-wiring in subpanel not to code 4-smoke alarm in living area not installed per manuf. instructions 5-smoke alarm required in bedroom 6-verify building is permitted for occupancy 7-this building appears to have been the laundry room |
|
| 10/31/2016 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999 * |