Permit Details

Status:
Expired
Type:
COMMERCIAL ALTERATION
Address:
1015 E BENSON HY
Address NEW:
1015 E BENSON HY
Apply Date:
02/24/2016
Applicant:
VINCE CATALANO
Description:
REPLACING A/C UNITS ON ROOF, GREASE TRAP AND EXAUST FANS
Contractors:
  • SKY SYSTEMS HEATING AND COOLING LLC

Permit Reviews

Permit Number - T16CM01348
Permit Status: Expired
Permit Description: REPLACING A/C UNITS ON ROOF, GREASE TRAP AND EXAUST FANS
Start Date Submittal Complete Date Status  
02/24/2016 WALK THRU - COMM 03/04/2016 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T16CM01348
Permit Status: Expired
Permit Description: REPLACING A/C UNITS ON ROOF, GREASE TRAP AND EXAUST FANS
Total Outstanding Activity Conditions - 1
Date Name
02/24/2016 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T16CM01348
Permite Description: REPLACING A/C UNITS ON ROOF, GREASE TRAP AND EXAUST FANS
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
04/12/2016 FIRE - KITCHEN EXH HOOD FINAL N/A Denied Tank 1 (In Box) - currently has 11 flow points. 1N (1), 260 (2), 2W (1), 230 (2). However, 2 fryers and charbroiler have no coverage.

Tank 2 - currently 10 flow points. 1N (4), 2W (2), 1F (2).

*To compensate for fryers and charbroiler, will need an additional 3-4 flow points. May need to add another tank, as well as pulling plans and permits.
*Griddle has 230 nozzles. 230 nozzles are rated for fryers not griddles.

Completed Inspections

Permit Status: Expired
Permit Number: T16CM01348
Permit Description: REPLACING A/C UNITS ON ROOF, GREASE TRAP AND EXAUST FANS
Total Completed Inspections - 2
Date Description Inspector Results Comments
04/12/2016 MECHANICAL - FINAL MRAMBER Approved IVRS - Inspection :*
11/07/2017 MECHANICAL - INTERMEDIATE MRAMBER Approved