Permit: T16CM01348

Parcel: 132130490


Addresses:

1015 E BENSON HY

Inspection Status: Denied

Inspection History: FIRE - KITCHEN EXH HOOD FINAL

Date Description Inspector Results Comments
04/12/2016 FIRE - KITCHEN EXH HOOD FINAL Denied Tank 1 (In Box) - currently has 11 flow points. 1N (1), 260 (2), 2W (1), 230 (2). However, 2 fryers and charbroiler have no coverage.

Tank 2 - currently 10 flow points. 1N (4), 2W (2), 1F (2).

*To compensate for fryers and charbroiler, will need an additional 3-4 flow points. May need to add another tank, as well as pulling plans and permits.
*Griddle has 230 nozzles. 230 nozzles are rated for fryers not griddles.