Inspection History Details
Inspection Status: Denied
Inspection History: FIRE - KITCHEN EXH HOOD FINAL
Permit Number - T16CM01348
Inspection Description - FIRE - KITCHEN EXH HOOD FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/12/2016 | FIRE - KITCHEN EXH HOOD FINAL | Denied | Tank 1 (In Box) - currently has 11 flow points. 1N (1), 260 (2), 2W (1), 230 (2). However, 2 fryers and charbroiler have no coverage. Tank 2 - currently 10 flow points. 1N (4), 2W (2), 1F (2). *To compensate for fryers and charbroiler, will need an additional 3-4 flow points. May need to add another tank, as well as pulling plans and permits. *Griddle has 230 nozzles. 230 nozzles are rated for fryers not griddles. |