Permit: T16BU00952
Permit Details
Apply Date:
06/22/2016
Applicant:
SIMPLEX GRINNELL L P
Description:
FIRE ALARM
Contractors:
- SIMPLEX GRINNELL L P
Outstanding Activity Conditions
Permit Number - T16BU00952
Permit Status: Final
Permit Description: FIRE ALARM
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
06/22/2016 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T16BU00952
Permit Description: FIRE ALARM
Total Completed Inspections - 1
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/14/2016 | FIRE - ALARM FINAL | nsprenger | Approved | What Passed: All AV devices, all pull stations ( at panel and signal sent), all water flows ( at panel and signal sent), 22 server rooms smokes worked ( at panel and set off preaction release), STILL NEED TO: 1) place lockout of FA circuit 2) test 3 heats in server room 3) test tampers on 1,2 floors would not restore, 3rd floor didnt send signal to panel 4) server room ( elec room) 2 underfloor smokes not activating preaction release 5). test all 6 elevator lobby smokes 6)test 5 duct detctors ( roof) 7) do 24 hr battery test 8)test battery tamper |