Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T16BU00952
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/11/2017 | FIRE - ALARM FINAL | Approved | ||
10/14/2016 | FIRE - ALARM FINAL | Denied | What Passed: All AV devices, all pull stations ( at panel and signal sent), all water flows ( at panel and signal sent), 22 server rooms smokes worked ( at panel and set off preaction release), STILL NEED TO: 1) place lockout of FA circuit 2) test 3 heats in server room 3) test tampers on 1,2 floors would not restore, 3rd floor didnt send signal to panel 4) server room ( elec room) 2 underfloor smokes not activating preaction release 5). test all 6 elevator lobby smokes 6)test 5 duct detctors ( roof) 7) do 24 hr battery test 8)test battery tamper |