Permit: T16BU00336
Permit Details
Apply Date:
03/03/2016
Applicant:
SIMPLEX GRINNELL L P
Description:
NEW FIRE ALARM SYSTEM I-1/I-2
Contractors:
- SIMPLEX GRINNELL L P
Outstanding Activity Conditions
Permit Number - T16BU00336
Permit Status: Final
Permit Description: NEW FIRE ALARM SYSTEM I-1/I-2
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 03/03/2016 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T16BU00336
Permit Description: NEW FIRE ALARM SYSTEM I-1/I-2
Total Completed Inspections - 1
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/28/2016 | FIRE - ALARM FINAL | JPEELDAVIS | Approved | ONLY BLDG # 5 PARTIAL ON THE PARTIAL Smoke detectors in rooms are too close to the ceiling fans (16 total) NFPA 72, 2010 29.8.3.4 Specific location requirements. The installation of smoke alarms and smoke detectors shall comply with the following requirements: # 7 Smoke alarms and smoke detectors shall not be installed within a 36" (910 mm) horizontal path from the tip of the bade of a ceiling - suspended (paddle) fan. Tested the smoke detectors, duct smoke detectors, water flow, tamper, horn strobes, strobe only, kitchen fire suppression system for proper operation. |