Permit Details

Status:
Final
Type:
COMMERCIAL OTHER
Address:
2720 E RIVER RD
Address NEW:
2720 E RIVER RD
Apply Date:
03/03/2016
Applicant:
SIMPLEX GRINNELL L P
Description:
NEW FIRE ALARM SYSTEM I-1/I-2
Contractors:
  • SIMPLEX GRINNELL L P

Outstanding Activity Conditions

Permit Number - T16BU00336
Permit Status: Final
Permit Description: NEW FIRE ALARM SYSTEM I-1/I-2
Total Outstanding Activity Conditions - 1
Date Name
03/03/2016 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T16BU00336
Permit Description: NEW FIRE ALARM SYSTEM I-1/I-2
Total Completed Inspections - 1
Date Description Inspector Results Comments
12/28/2016 FIRE - ALARM FINAL JPEELDAVIS Approved ONLY BLDG # 5 PARTIAL ON THE PARTIAL

Smoke detectors in rooms are too close to the ceiling fans (16 total)
NFPA 72, 2010 29.8.3.4 Specific location requirements. The installation of smoke alarms and smoke detectors shall comply with the following requirements: # 7 Smoke alarms and smoke detectors shall not be installed within a 36" (910 mm) horizontal path from the tip of the bade of a ceiling - suspended (paddle) fan.

Tested the smoke detectors, duct smoke detectors, water flow, tamper, horn strobes, strobe only, kitchen fire suppression system for proper operation.

Documents

File Name Document Type  
001_ALARM.TIF FIRE PLANS VIEW
002_ALARM.TIF FIRE PLANS VIEW
003_ALARM.TIF FIRE PLANS VIEW
004_ALARM.TIF FIRE PLANS VIEW
005_ALARM.TIF FIRE PLANS VIEW
006_ALARM.TIF FIRE PLANS VIEW
007_ALARM.TIF FIRE PLANS VIEW
008_ALARM.TIF FIRE PLANS VIEW
009_ALARM.TIF FIRE PLANS VIEW
010_ALARM.TIF FIRE PLANS VIEW
None DOCUMENTS VIEW