Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T16BU00336
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/01/2017 | FIRE - ALARM FINAL | Approved | already approved | |
| 01/17/2017 | FIRE - ALARM FINAL | Partial Approval | 1) need pretest on bldg 4 2) need ROC/72 |
|
| 01/10/2017 | FIRE - ALARM FINAL | Partial Approval | Ground Fault on FACP could NOT test today. Tested the kitchen fire suppression system in Bldg 4 passed. Tested the fire sprinkler system 47 seconds, tamper switch tested ok. | |
| 12/28/2016 | FIRE - ALARM FINAL | Partial Approval | ONLY BLDG # 5 PARTIAL ON THE PARTIAL Smoke detectors in rooms are too close to the ceiling fans (16 total) NFPA 72, 2010 29.8.3.4 Specific location requirements. The installation of smoke alarms and smoke detectors shall comply with the following requirements: # 7 Smoke alarms and smoke detectors shall not be installed within a 36" (910 mm) horizontal path from the tip of the bade of a ceiling - suspended (paddle) fan. Tested the smoke detectors, duct smoke detectors, water flow, tamper, horn strobes, strobe only, kitchen fire suppression system for proper operation. |
|
| 11/08/2016 | FIRE - ALARM FINAL | Partial Approval | Only Bldg #3 approved/finaled. | |
| 07/28/2016 | FIRE - ALARM FINAL | Partial Approval | Only Bldg #2 approved/finaled. |