Permit: T16BU00336

Parcel: 10824008F


Addresses:

2720 E RIVER RD


Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Permit Number - T16BU00336

Inspection Description - FIRE - ALARM FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/01/2017 FIRE - ALARM FINAL Approved already approved
01/17/2017 FIRE - ALARM FINAL Partial Approval 1) need pretest on bldg 4
2) need ROC/72
01/10/2017 FIRE - ALARM FINAL Partial Approval Ground Fault on FACP could NOT test today. Tested the kitchen fire suppression system in Bldg 4 passed. Tested the fire sprinkler system 47 seconds, tamper switch tested ok.
12/28/2016 FIRE - ALARM FINAL Partial Approval ONLY BLDG # 5 PARTIAL ON THE PARTIAL

Smoke detectors in rooms are too close to the ceiling fans (16 total)
NFPA 72, 2010 29.8.3.4 Specific location requirements. The installation of smoke alarms and smoke detectors shall comply with the following requirements: # 7 Smoke alarms and smoke detectors shall not be installed within a 36" (910 mm) horizontal path from the tip of the bade of a ceiling - suspended (paddle) fan.

Tested the smoke detectors, duct smoke detectors, water flow, tamper, horn strobes, strobe only, kitchen fire suppression system for proper operation.
11/08/2016 FIRE - ALARM FINAL Partial Approval Only Bldg #3 approved/finaled.
07/28/2016 FIRE - ALARM FINAL Partial Approval Only Bldg #2 approved/finaled.