Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T16BU00289
Permit Details
Apply Date:
02/25/2016
Applicant:
SLETTEN CONSTRUCTION COMPANY
Description:
SPRINKLER
Contractors:
- SLETTEN CONSTRUCTION COMPANY
Outstanding Activity Conditions
Permit Number - T16BU00289
Permit Status: Final
Permit Description: SPRINKLER
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
02/25/2016 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T16BU00289
Permit Description: SPRINKLER
Total Completed Inspections - 2
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/29/2016 | FIRE SPKLR - UG, PIPING, HYDRO | CCLARK | Approved | |
03/29/2016 | FIRE SPKLR - UG PIPING FLUSH | nsprenger | Approved | Flushed at stub up ( 8 Inch hose connected to a 6 inch hose and flushed without burlap sack for 1 minute at full capacity. Flushed with burlap attached after that for 1 minute more at full capacity. Water ran clear both times. No debris found in burlap sach after second flush. Received copy of Contractors Material and Test Certificate for Underground Piping ( to be scanned to FRMS). May connect to Riser. |