Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Details

Status:
Final
Type:
COMMERCIAL OTHER
Apply Date:
02/25/2016
Applicant:
SLETTEN CONSTRUCTION COMPANY
Description:
SPRINKLER
Contractors:
  • SLETTEN CONSTRUCTION COMPANY

Outstanding Activity Conditions

Permit Number - T16BU00289
Permit Status: Final
Permit Description: SPRINKLER
Total Outstanding Activity Conditions - 1
Date Name
02/25/2016 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T16BU00289
Permit Description: SPRINKLER
Total Completed Inspections - 2
Date Description Inspector Results Comments
02/29/2016 FIRE SPKLR - UG, PIPING, HYDRO CCLARK Approved
03/29/2016 FIRE SPKLR - UG PIPING FLUSH nsprenger Approved Flushed at stub up ( 8 Inch hose connected to a 6 inch hose and flushed without burlap sack for 1 minute at full capacity. Flushed with burlap attached after that for 1 minute more at full capacity. Water ran clear both times. No debris found in burlap sach after second flush. Received copy of Contractors Material and Test Certificate for Underground Piping ( to be scanned to FRMS). May connect to Riser.

Documents

File Name Document Type  
001_SPKLR.TIF FIRE PLANS VIEW
None DOCUMENTS VIEW