Permit: T16BU00289

Parcel: 13323164A


Addresses:

7150 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: FIRE SPKLR - UG PIPING FLUSH

Date Description Inspector Results Comments
03/29/2016 FIRE SPKLR - UG PIPING FLUSH Approved Flushed at stub up ( 8 Inch hose connected to a 6 inch hose and flushed without burlap sack for 1 minute at full capacity. Flushed with burlap attached after that for 1 minute more at full capacity. Water ran clear both times. No debris found in burlap sach after second flush. Received copy of Contractors Material and Test Certificate for Underground Piping ( to be scanned to FRMS). May connect to Riser.
03/01/2016 FIRE SPKLR - UG PIPING FLUSH Not ready for Inspection Unable to locate pipes needed for flush. Will reschedule. C.C