Inspection Status: Approved
Inspection History: FIRE SPKLR - UG PIPING FLUSH
| Date |
Description |
Inspector |
Results |
Comments |
| 03/29/2016 |
FIRE SPKLR - UG PIPING FLUSH |
|
Approved |
Flushed at stub up ( 8 Inch hose connected to a 6 inch hose and flushed without burlap sack for 1 minute at full capacity. Flushed with burlap attached after that for 1 minute more at full capacity. Water ran clear both times. No debris found in burlap sach after second flush. Received copy of Contractors Material and Test Certificate for Underground Piping ( to be scanned to FRMS). May connect to Riser. |
| 03/01/2016 |
FIRE SPKLR - UG PIPING FLUSH |
|
Not ready for Inspection |
Unable to locate pipes needed for flush. Will reschedule. C.C |