Permit: T15CM04105
Permit Details
Apply Date:
06/17/2015
Applicant:
TEMPERATURE CONTROLS, *APA*
Description:
REPL 3.5 SPLIT SYSTEM LIKE FOR LIKE;RES
Contractors:
- TEMPERATURE CONTROLS, *APA*
Outstanding Activity Conditions
Permit Number - T15CM04105
Permit Status: Expired
Permit Description: REPL 3.5 SPLIT SYSTEM LIKE FOR LIKE;RES
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 06/17/2015 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T15CM04105
Permite Description: REPL 3.5 SPLIT SYSTEM LIKE FOR LIKE;RES
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/21/2015 | MECHANICAL - FINAL | N/A | Partial Approval | ADHESIVE TAPE NOT APPROVED FOR USE OUTDOORS OR LINE SET. USE ROOD COATING. CONDENSATE CANNOT TERMINATE INTO A SEWER VENT. PROVIDE HOSE CLAMP AT BOTH ENDS OF PLASTIC DRAIN HOSE. PROVIDE THE REQUIRED GFI SERVICE RECEPTACLE ON ROOF. |