Inspection Status: Partial Approval
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/21/2015 |
MECHANICAL - FINAL |
|
Partial Approval |
ADHESIVE TAPE NOT APPROVED FOR USE OUTDOORS OR LINE SET. USE ROOD COATING. CONDENSATE CANNOT TERMINATE INTO A SEWER VENT. PROVIDE HOSE CLAMP AT BOTH ENDS OF PLASTIC DRAIN HOSE. PROVIDE THE REQUIRED GFI SERVICE RECEPTACLE ON ROOF. |