Permit Details

Status:
Expired
Type:
COMMERCIAL ALTERATION
Address:
750 N KOLB RD
Apply Date:
02/10/2015
Applicant:
GOLDSTEIN GENE
Description:
ADD BAR AND APPLIANCES TO PATIO AREA
Architects:
  • GOLDSTEIN GENE
Contractors:
  • INNOVATIVE TECHNOLOGY DEVELOPMENT GROUP LLC

Permit Reviews

Permit Number - T15CM00870
Permit Status: Expired
Permit Description: ADD BAR AND APPLIANCES TO PATIO AREA
Start Date Submittal Complete Date Status  
02/10/2015 COMMERCIAL - TI 04/16/2018 COMPLETED Review Details
04/16/2018 REVISION - - 1ST 04/17/2018 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T15CM00870
Permit Status: Expired
Permit Description: ADD BAR AND APPLIANCES TO PATIO AREA
Total Outstanding Activity Conditions - 1
Date Name
02/10/2015 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T15CM00870
Permite Description: ADD BAR AND APPLIANCES TO PATIO AREA
Total Outstanding Inspections - 9
Last Inspection Date Description Inspector Results Comments
ELECTRIC - ABOVE CEILING N/A Not Inspected
ELECTRIC - OUTDOOR LIGHTING N/A Not Inspected
OUTDOOR LIGHTING FINAL N/A Not Inspected
04/08/2015 BUILDING - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
04/08/2015 BUILDING - FINAL N/A Denied PROVIDE ADDITIONAL INFO ON CITY PLAN; PLAN DOES NOT INDICATE THAT PATIO WALL IS PART OF A CONDEMNED BUILDING. THERE ARE NO SANITARY FACILITIES. OCCUPANT LOAD SIGN INDICATES 150 PEOPLE. YOU WILL NEED BUILDING OFFICIALS PERMISSION TO OCCUPY. IN ADDITION TO A PEDDLERS PERMIT.
04/08/2015 ELECTRIC - UNDERGROUND N/A Not ready for Inspection IVRS - Inspection :*
04/08/2015 ELECTRIC - INTERMEDIATE N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
04/08/2015 ELECTRIC - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
04/08/2015 ELECTRIC - FINAL N/A Denied CORRECT; EMERGENCY LIGHTING CIRCUIT PER PLAN, IMPROPER WIRING METHODS ON EXTERIOR LIGHTING. SUB-PANEL REQUIRES; GROUNDING EQUIP CONDUCTOR, PROTECTIVE BUSHINGS, ID GROUNDED CONDUCTOR, PLUG HOLE, PROVDE PROPER USE OF REDUCING BUSHINGS. BOND OR REMOVE GROUNDING ELECTRODE RACEWAY. PROPER LANDING OF STRANDED WIRES.

Completed Inspections

Permit Status: Expired
Permit Number: T15CM00870
Permit Description: ADD BAR AND APPLIANCES TO PATIO AREA
Total Completed Inspections - 6
Date Description Inspector Results Comments
04/06/2015 RIGHT OF WAY - FINAL RLEDONNE Approved
04/06/2015 NPPO - FINAL RLEDONNE Approved
04/06/2015 SIGN - FINAL RLEDONNE Approved
04/06/2015 LANDSCAPE - FINAL RLEDONNE Approved
04/06/2015 ENGINEERING - FINAL RLEDONNE Approved
04/07/2015 FIRE - FINAL nsprenger Approved Approved.
Occ Load sign in place.
Fire extinguisher mounted by West Exit.
Exit signs and back up emergency lights operated correctly on power shut off.

Documents

File Name Document Type  
001_TS1.TIF CONSTRPLANS VIEW
002_A1.0.TIF CONSTRPLANS VIEW
003_E1.0TIF CONSTRPLANS VIEW
004_E.2.TIF CONSTRPLANS VIEW
None DOCUMENTS VIEW