Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T15CM00870
Parcel: 13323193C

Address:
750 N KOLB RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM00870
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/10/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
02/10/2015 JASON GREEN ENGINEERING REVIEW Approved
02/10/2015 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
03/27/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
03/31/2015 KEN BROUILLETTE FIRE REVIEW Approved
04/01/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
04/01/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
04/01/2015 ROBERT SHERRY WATER REVIEW Completed
04/01/2015 RSHERRY1 WWM REVIEW Passed No wastewater plumbing.
04/02/2015 MICHAEL ST. PAUL ZONING REVIEW Approved