Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T15BU01311
Permit Details
Apply Date:
11/10/2015
Applicant:
CODI-LEE SCARBROUGH
Description:
ALARM
Contractors:
- FAVARAS AUTOMATIC FIRE DETECTION AND COMUNICATIO
Outstanding Activity Conditions
Permit Number - T15BU01311
Permit Status: Final
Permit Description: ALARM
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
11/10/2015 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T15BU01311
Permit Description: ALARM
Total Completed Inspections - 1
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/19/2015 | FIRE - ALARM FINAL | nsprenger | Approved | on Phase 1 Sam Levitz side Tested and Passed duct detectors on roof ( 4) - signals received supervisory smokes ( 2) above FACP and Aux Power unit second floor - signals received Flow #1 - 38 Sec signals received #2 - 48 sec signals received Tamper #1 working - siganls received #2 working - signals received #3 working - signals received pull station - working - signals received Horn / Strobes - working and devices as per plan FACP - power out - batteries working - signal received batter disconnect - working - signal received |